Pagina 1 - Programming Guide

MAKING MODERN LIVING POSSIBLEProgramming GuideVLT® HVAC Drive

Pagina 2 - 3 Parameter Description

2 How to Programme2.1 Local Control Panel2.1.1 How to Operate Graphical LCP (GLCP)The following instructions are valid for the GLCP (LCP 102).The GLC

Pagina 3

13-01 Start EventOption: Function:[22] Comparator 0 Use the result of comparator 0 in thelogic rule.[23] Comparator 1 Use the result of comparator 1

Pagina 4

13-02 Stop EventOption: Function:[8] Below I low See parameter group 5-3* for furtherdescription.[9] Above I high See parameter group 5-3* for furthe

Pagina 5

13-02 Stop EventOption: Function:[51] Comparator 5 Use the result of comparator 5 in thelogic rule.[60] Logic rule 4 Use the result of logic rule 4 i

Pagina 6

13-10 Comparator OperandArray [4]Option: Function:[68] Below I low[69] Above I high[70] Out of speed range[71] Below speed low[72] Above speed high[7

Pagina 7 - 6 MG11CD02 - VLT

3.13.4 13-2* TimersUse the result (TRUE or FALSE) from timers directly todefine an event (see 13-51 SL Controller Event), or asboolean input in a logi

Pagina 8

13-40 Logic Rule Boolean 1Array [6]Option: Function:[24] Comparator 2 Use the result of comparator 2 in thelogic rule.[25] Comparator 3 Use the resul

Pagina 9 - High Voltage

13-41 Logic Rule Operator 1Array [6]Option: Function:Select the first logical operator to use onthe Boolean inputs from 13-40 Logic RuleBoolean 1 and

Pagina 10 - 2 How to Programme

13-42 Logic Rule Boolean 2Array [6]Option: Function:[91] ECB Bypass Mode[92] ECB Test Mode[100] Fire Mode13-43 Logic Rule Operator 2Array [6]Option:

Pagina 11 - 10 MG11CD02 - VLT

13-44 Logic Rule Boolean 3Array [6]Option: Function:[81] Dry Pump[82] End of Curve[83] Broken Belt[90] ECB Drive Mode[91] ECB Bypass Mode[92] ECB Tes

Pagina 12 - MG11CD02 - VLT

13-52 SL Controller ActionArray [20]Option: Function:[2] Select set-up 1Changes the active set-up (0-10 ActiveSet-up) to ‘1’.[3] Select set-up 2Chang

Pagina 13 - 12 MG11CD02 - VLT

It is possible to toggle between three status read-outdisplays by pressing the [Status] key.Operating variables with different formatting are shown in

Pagina 14 - Setup 1

3.14 Main Menu - Special Functions -Group 143.14.1 14-0* Inverter Switching 14-00 Switching PatternOption: Function:Select the switching pattern: 60

Pagina 15 - 14 MG11CD02 - VLT

DC VoltageOutput Speed rpmOver Voltage Control LevelMainsTime130BT101.10Par 14-11Illustration 3.5 Controlled Ramp down - short mains failure.Ramping d

Pagina 16 - 130BP064.10

14-22 Operation ModeOption: Function:Use this parameter to specify normal operation,to perform tests or to initialise all parametersexcept 15-03 Powe

Pagina 17 - 2.1.6 Function Set-ups

14-29 Service CodeRange: Function:0 * [-2147483647 - 2147483647 ] Service use only.3.14.3 14-3* Current Limit ControlThe frequency converter featur

Pagina 18 - 130BA115.10

3.14.5 14-5* EnvironmentThese parameters help the frequency converter to operateunder special environmental conditions.3.14.6 14-50 RFI Filter14-50 R

Pagina 19 - How to Programme

3.14.8 No Trip at Inverter OverloadIn some pump systems, the frequency converter has notbeen sized properly to yield the current needed in allpoints o

Pagina 20 - 2.1.8 Parameter Selection

3.15 Main Menu - Drive Information - Group 15Parameter group containing frequency converterinformation such as operating data, hardware configu-ratio

Pagina 21 - 130BP069.10

15-10 Logging SourceArray [4]Option: Function:[1627] Power Filtered [hp][1630] DC Link Voltage[1632] Brake Energy /s[1633] Brake Energy /2 min[1634]

Pagina 22

15-14 Samples Before TriggerRange: Function:50 * [0 - 100 ] Enter the percentage of all samples prior to atrigger event which are to be retained in

Pagina 23

3.15.4 15-3* Alarm LogParameters in this group are array parameters, where up to10 fault logs can be viewed. [0] is the most recent loggeddata, and [9

Pagina 24 - 3.2.1 0-0* Basic Settings

OnWarn.Alarm130BP044.10GLCP keys Menu keysThe menu keys are divided into functions. The keys belowthe display and indicator lamps are used for paramet

Pagina 25 - * Set-up 1

3.15.6 15-6* Option Ident. This read-only parameter group contains information aboutthe hardware and software configuration of the optionsinstalled in

Pagina 26 - * Not linked

3.16 Main Menu - Data Readouts - Group 1616-00 Control WordRange: Function:0 * [0 - 65535 ] View the Control word sent from thefrequency converter

Pagina 27 - * [-2147483648

16-16 Torque [Nm]Range: Function:0.0Nm* [-30000.0 -30000.0Nm]View the torque value with sign, applied tothe motor shaft. Linearity is not exactbetwe

Pagina 28

16-39 Control Card Temp.Range: Function:0 °C* [0 - 100 °C] View the temperature on the control card,stated in °C16-40 Logging Buffer FullOption: F

Pagina 29

16-56 Feedback 3 [Unit]Range: Function:0.000ProcessCtrlUnit* [-999999.999 -999999.999ProcessCtrlUnit]View value of Feedback 3,see parameter group 20

Pagina 30 - * Frequency

16-69 Pulse Output #27 [Hz]Range: Function:0 * [0 - 40000 ] View the actual value of impulses applied toterminal 27 in digital output mode.16-70 P

Pagina 31 - Cubic Unit (Power)

3.16.6 16-9* Diagnosis Read-Outs16-90 Alarm WordRange: Function:0 * [0 - 4294967295 ] View the alarm word sent via the serialcommunication port in

Pagina 32 - 3.2.5 0-4* LCP Keypad

16-96 Maintenance WordRange: Function:The third digit 0 indicates that no items fromthe second row requires maintenanceThe fourth digit A refers to t

Pagina 33 - 3.2.7 0-6* Password

3.17 Main Menu - Data Readouts 2 - Group 183.17.1 18-0* Maintenance LogThis group contains the last 10 Preventive Maintenanceevents. Maintenance Log

Pagina 34 - 0-7* Clock Settings

18-12 Fire Mode Log: Date and TimeRange: Function:Sizerelated* [ 0 -0 ]This parameter contains an array with 10elements. The parameter shows at whic

Pagina 35

Navigation KeysThe four navigation arrows are used to navigate betweenthe different choices available in [Quick Menu], [MainMenu] and [Alarm Log]. Use

Pagina 36 - 3.3.1 1-0* General Settings

3.18 Main Menu - FC Closed Loop - Group 20This parameter group is used for configuring the closed loop PID Controller, that controls the output frequ

Pagina 37

NOTEIf a feedback is not used, its source must be set to NoFunction [0]. 20-20 Feedback Function determines how thethree possible feedbacks will be us

Pagina 38 - 1-14 - 1-17 VVC

NOTEThis parameter is only available when using pressure totemperature feedback conversion.If the choice Linear [0] is selected in 20-01 Feedback 1Con

Pagina 39 - 3.3.4 1-2* Motor Data

20-14 Maximum Reference/Feedb.Range: Function:100.000ProcessCtrlUnit* [ par. 20-13 -999999.999ProcessCtrlUnit]Enter the maximumreference/feedback fo

Pagina 40 - * Off No function

20-20 Feedback FunctionOption: Function:setpoint reference. If all feedback signals areabove their corresponding setpoints, the PIDController will us

Pagina 41 - * [ 0.000 - 0.000

The difference between the two is illustrated by the following examples:Example 1 – Multi zone, single setpointIn an office building, a VAV (variable

Pagina 42 - * [ 10. - 9000

20-23 Setpoint 3Range: Function:0.000ProcessCtrlUnit* [ par. 20-13 -par. 20-14ProcessCtrlUnit]Setpoint 3 is used inClosed Loop Mode to entera setpoi

Pagina 43

20-36 Fan 2 Area [m2]Range: Function:0.500m2* [0.000 -10.000m2]20-37 Fan 2 Area [in2]Range: Function:Used for setting the area of the air ducts inc

Pagina 44

0 (zero). 20-81 PID Normal/ Inverse Control is determinedduring tuning process.These calculated values are presented on the LCP and theuser can decide

Pagina 45 - * [0.0 - 120.0 s]

20-81 PID Normal/ Inverse ControlOption: Function:[0] * NormalNormal [0] causes the frequency converter’s outputfrequency to decrease when the feedba

Pagina 46

130BA191.101Auto onResetHand onOMenuStatusQuickSetupMainMenuBack234OKOnAlarmWarn.SetupIllustration 2.1 Numerical LCP (NLCP)130BP077.1022.8rpmSetup 1

Pagina 47 - 3.3.9 1-8* Stop Adjustments

20-94 PID Integral TimeRange: Function:20.00s* [0.01 -10000.00s]Over time, the integrator accumulates acontribution to the output from the PIDcontro

Pagina 48 - * ETR trip 1

3.19 Main Menu - Extended Closed Loop - Group 21The FC 102 offers 3 Extended Closed Loop PID controllersin addition to the PID Controller. These can

Pagina 49

21-02 PID Output ChangeRange: Function:0.10 * [0.01 -0.50 ]This parameter sets the magnitude of stepchange during autotuning. The value is apercent

Pagina 50 - 3.4.1 2-0* DC-Brakes

21-10 Ext. 1 Ref./Feedback UnitOption: Function:[73] kPa[74] m WG[75] mm Hg[80] kW[120] GPM[121] gal/s[122] gal/min[123] gal/h[124] CFM[125] ft³/s[12

Pagina 51

21-15 Ext. 1 SetpointRange: Function:0.000ExtPID1Unit* [ par. 21-11 -par. 21-12ExtPID1Unit]The setpoint reference isused in extended 1 closedloop. E

Pagina 52 - * Enabled Activates OVC

3.19.4 21-3* Closed Loop 2 Ref/Fb21-30 Ext. 2 Ref./Feedback UnitOption: Function:See 21-10 Ext. 1 Ref./Feedback Unit for details[0] None[1] * %[5] PP

Pagina 53 - 3.5.2 3-1* References

21-35 Ext. 2 SetpointRange: Function:0.000 ExtPID2Unit* [ par. 21-31 - par.21-32 ExtPID2Unit]See 21-15 Ext. 1Setpoint for details.21-37 Ext. 2 Ref

Pagina 54 - 130BA059.12

21-51 Ext. 3 Minimum ReferenceRange: Function:0.000 ExtPID3Unit* [ -999999.999 - par.21-52 ExtPID3Unit]See 21-11 Ext. 1Minimum Referencefor details

Pagina 55 - 3.5.3 3-4* Ramp 1

3.20 Main Menu - Application Functions - Group 22This group contains parameters used for monitoring VLT®HVAC Drive applications.22-00 External Inter

Pagina 56 - 3.5.4 3-5* Ramp 2

NOTECarry out No Flow tuning before setting the PI controller parameters!FC130BA253.10P130BA254.10HeadFlow21No Flow Detection is based on the measurem

Pagina 57 - 3.5.5 3-8* Other Ramps

If no external stop function is selected and the [Off] key isinactive the motor can be stopped by disconnecting themains supply.[Auto On] enables the

Pagina 58 - * [-200 - 200

Dry pump detection:No Flow Detection can also be used for detecting if thepump has run dry (low power consumption-high speed).Can be used with both th

Pagina 59 - 3.6.1 4-1* Motor Limits

22-24 No-Flow DelayRange: Function:10 s* [1 - 600 s] Set the time Low Power/Low Speed must staydetected to activate signal for actions. Ifdetection

Pagina 60 - 4-5* Adj. Warnings

22-32 Low Speed [RPM]Range: Function:Sizerelated* [ 0 - par.22-36 RPM]To be used if 0-02 Motor Speed Unithas been set for RPM (parameter notvisible

Pagina 61 - 3.6.3 4-6* Speed Bypass

(if enabled) to start de-staging of lag pumps (fixed speed)before stopping the lead pump (variable speed).When entering Sleep Mode, the lower status l

Pagina 62

When low power or low speed is detected the motor isstopped, but the reference signal (fref) from the externalcontroller is still monitored and becaus

Pagina 63 - * PNP - Active

22-45 Setpoint BoostRange: Function:0%* [-100- 100%]Only to be used if 1-00 Configuration Mode, is setfor Closed Loop and the integrated PI controll

Pagina 64

broken belt function (22-60 Broken Belt Function) isperformed22-60 Broken Belt FunctionSelects the action to be performed if the Broken Belt conditio

Pagina 65

HDESIGN (Required pressure) is the setpoint for closed loop(PI) operation of the frequency converter and is set as forclosed loop operation without fl

Pagina 66

Control Curve(head)(ow)HQ130BA388.11100%P22-81 0%22-82 Work Point CalculationOption: Function:Example 1: Speed at System Design Working Pointis kn

Pagina 67 - 5-3* Digital Outputs

22-84 Speed at No-Flow [Hz]Range: Function:Sizerelated* [ 0.0 -par.22-86 Hz]Resolution 0.033 Hz.The speed of the motor at which flow haseffectively

Pagina 68

6. To move to a different digit within a parametersetting, use the [◀] and [▶] buttons7. Highlighted area indicates digit selected forchange8. Press [

Pagina 69

3.21 Main Menu - Time-based Functions - Group 233.21.1 23-0* Timed Actions Use Timed Actions for actions needing to be performed ona daily or weekly

Pagina 70 - 3.7.6 5-4* Relays

23-01 ON ActionArra [10]Option: Function:[36] Set digital out E low[37] Set digital out F low[38] Set digital out A high[39] Set digital out B high[4

Pagina 71 - 5-5* Pulse Input

23-08 Timed Actions ModeUsed to enable and disable automatic timed actions.Option: Function:[0] * Timed Actions Auto Enable timed actions.[1] Timed A

Pagina 72 - 130BA076.10

+-+---++++++++++++++++++130BA492.10Untitled - MCT 10 SET - up SoftwareFile Edit View Insert Communication Tools Options HelpID Name Setup 1 S

Pagina 73 - * [0 - 32000 Hz]

23-11 Maintenance ActionOption: Function:Select the action to be associated withthe Preventive Maintenance Event.[1] Lubricate[2] Clean[3] Replace[4]

Pagina 74 - 3.7.9 5-9* Bus Controlled

23-16 Maintenance TextRange: Function:The text is written according to the guidelines in 0-37 Display Text 1.3.21.3 23-5* Energy LogThe frequency con

Pagina 75

23-51 Period StartRange: Function:Sizerelated* [ 0 -0 ]Set the date and time at which the EnergyLog starts update of the counters. First datawill be

Pagina 76 - 130BA038.13

exceed rated value, but those registrations will be includedin 90%-100% (MAX) counter.Relative valueoperating variableCounter 1: +1Counter 0: +5Counte

Pagina 77 - 3.8.3 6-2* Analog Input 2

23-63 Timed Period StartRange: Function:Size related* [ 0 - 0 ] Set the date and time at which theTrending starts the update of the TimedBin counte

Pagina 78

Cost Savings ={∑t=0t(Rated Motor Power ∗Power Reference Factor)−Actual Power Consumption ×Energy Cost}− Investment CostBreak even (payback) occurs

Pagina 79 - 3.8.6 6-5* Analog Output 1

Parameter [Units]0-01 Language 1-20 Motor Power [kW][kW]1-21 Motor Power [HP][HP]1-22 Motor Voltage*[V]1-23 Motor Frequency[Hz]1-24 Motor Current[A]1-

Pagina 80

3.22 Main Menu - Application Functions 2 - Group 243.22.1 24-0* Fire ModeCAUTIONPlease note the frequency converter is only onecomponent of the VLT®

Pagina 81

NOTEIf in Fire Mode it is desired to use the Live Zero function,then it will also be active for analog inputs other than thatused for Fire Mode setpoi

Pagina 82

24-02 Fire Mode UnitOption: Function:[122] gal/min[123] gal/h[124] CFM[125] ft³/s[126] ft³/min[127] ft³/h[130] lb/s[131] lb/min[132] lb/h[140] ft/s[1

Pagina 83 - * Option A

24-09 Fire Mode Alarm HandlingOption: Function:[0] Trip+Reset,CriticalAlarmsIf this mode is selected, the frequencyconverter will continue to run, ig

Pagina 84 - * FC profile

24-10 Drive Bypass FunctionOption: Function:This parameter determines, what circumstanceswill activate the Drive Bypass Function:[0] * Disabled[1] En

Pagina 85 - 3.9.3 8-3* FC Port Settings

24-96 Locked Rotor Coefficient 1Range: Function:0.0000 * [-10.0000 -10.0000 ]Enter the cubic coefficient of theLocked Rotor detection functionmulti

Pagina 86 - 3.9.4 8-4* Telegram Selection

3.23 Main Menu - Cascade Controller - Group 25Parameters for configuring the Basic Cascade Controller for sequence control of multiple pumps. For a m

Pagina 87 - * Digital

3.23.1 25-0* System SettingsParameters related to control principles and configurationof the system.25-00 Cascade ControllerOption: Function:For oper

Pagina 88 - 3.9.8 8-9* Bus Jog

25-20 Staging BandwidthRange: Function:10%* [ 1 -par.25-21%]Set the staging bandwidth (SBW) percentage toaccommodate normal system pressure fluctuat

Pagina 89 - * [-200 - 200 ]

25-23 SBW Staging DelayRange: Function:15s* [1 -3000 s]Immediate staging of a fixed speed pump is notdesirable when a momentary pressure drop in the

Pagina 90

Step 6: Choose 6-50 Terminal 42 Output. Press [OK].130BA115.106 - 50 Terminal 42 Output(100) Output frequency26.3% 5.82A

Pagina 91 - * [ 0

25-29 Destage FunctionOption: Function:The Destage Function ensures that the lowestnumbers of pumps are running to save energyand to avoid dead head

Pagina 92 - * Enable

NOTEIf the set-point is reached after staging before the variablespeed pump reaches its minimum speed - the system willenter the state closed loop as

Pagina 93

25-47 Destaging Speed [Hz]Range: Function:0.0Hz* [0.0- 0.0Hz]Readout of the below calculated value forDestaging Speed. When removing a fixed speedpu

Pagina 94

25-54 Alternation Predefined TimeRange: Function:Sizerelated* [ 0 -0 ]If optionPredefined Time [3] in 25-51 Alternation Event, is selected, thevaria

Pagina 95 - 3.11.3 10-1* DeviceNet

3.23.5 25-8* StatusReadout parameters informing about the operating statusof the Cascade Controller and the pumps controlled.25-80 Cascade StatusRang

Pagina 96

3.24 Main Menu - Analog I/O Option MCB 109 - Group 26The Analog I/O Option MCB 109 extends the functionality of VLT® HVAC Drive frequency converters,

Pagina 97 - 3.11.5 10-3* Parameter Access

NOTEThe maximum current for the analog outputs 0-10V is 1mA.NOTEWhere Live Zero Monitoring is used, it is important that any analog inputs not being u

Pagina 98

3.24.1 26-0* Analog I/O ModeParameter group for setting up the analog I/O configu-ration. The option is equipped with 3 analog inputs. Theseanalog inp

Pagina 99 - 13-0* SLC Settings

26-15 Term. X42/1 High Ref./Feedb. ValueRange: Function:100.000 * [-999999.999 -999999.999 ]Enter the analog input scalingvalue that corresponds to

Pagina 100

26-34 Term. X42/5 Low Ref./Feedb. ValueRange: Function:0.000 * [-999999.999 -999999.999 ]Enter the analog input scalingvalue that corresponds to th

Pagina 101

Q3-3 Closed Loop SettingsQ3-30 Single Zone Int. Set Point Q3-31 Single Zone Ext. Set Point Q3-32 Multi Zone / Adv1-00 Configuration Mode 1-00 Configur

Pagina 102 - 3.13.3 13-1* Comparators

26-43 Terminal X42/7 Bus ControlRange: Function:0.00 %* [0.00 - 100.00 %] Holds the level of terminal X42/7 ifcontrolled by bus.26-44 Terminal X42

Pagina 103 - * [-100000.000

26-60 Terminal X42/11 OutputOption: Function:[102] Feedback +-200%-200% to +200% of 20-14 MaximumReference/Feedb., (0-20 mA)[103] Motor cur. 0-Imax0

Pagina 104 - 3.13.5 13-4* Logic Rules

4 Troubleshooting4.1 TroubleshootingA warning or an alarm is signalled by the relevant LED onthe front of the frequency converter and indicated by ac

Pagina 105

No. Description Warning Alarm/TripAlarm/Trip Lock Parameter Reference23 Internal Fan Fault X 24 External Fan Fault X 14-5325 Brake resistor s

Pagina 106 - * DISABLED

No. Description Warning Alarm/TripAlarm/Trip Lock Parameter Reference93 Dry Pump X X 22-2*94 End of Curve X X 22-5*95 Broken Belt X X 22-6*96 St

Pagina 107

Alarm Word and Extended Status WordBit Hex Dec Alarm Word Warning Word Extended Status Word0 00000001 1 Brake Check Brake Check Ramping1 00000002 2 Pw

Pagina 108 - * Disabled

4.1.1 Alarm Words16-90 Alarm WordBit(Hex)Alarm Word(16-90 Alarm Word)0000000100000002 Power card over temperature00000004 Earth fault0000000800000010

Pagina 109

4.1.2 Warning Words16-92 Warning WordBit(Hex)Warning Word(16-92 Warning Word)00000001 00000002 Power card over temperature00000004 Earth fault0000000

Pagina 110 - * 5.0 kHz

4.1.3 Extended Status WordsExtended status word, 16-94 Ext. Status WordBit(Hex)Extended Status Word(16-94 Ext. Status Word)00000001 Ramping00000002 AM

Pagina 111 - Over Voltage Control Level

4.1.4 Fault MessagesThe warning/alarm information below defines eachwarning/alarm condition, provides the probable cause forthe condition, and details

Pagina 112 - * No action

Contents1 Introduction31.1.1 Copyright, Limitation of Liability and Revision Rights 31.1.2 Approvals 31.1.3 Symbols 31.1.4 Abbreviations 41.1.6 Defi

Pagina 113 - 3.14.4 14-4*Energy Optimising

Q3-4 Application SettingsQ3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions22-60 Broken Belt Function 22-20 Low Power Auto Set-up 1-0

Pagina 114 - 3.14.7 14-6* Auto Derate

Ensure that Motor data in parameters 1-20through 1-25 are set correctly.If an external fan is in use, check in 1-91 MotorExternal Fan that it is selec

Pagina 115 - * [50 - 100

Verify a proper installation based on EMCrequirements.ALARM 18, Start failedThe speed has not been able to exceed 1-77 CompressorStart Max Speed [RPM]

Pagina 116 - 3.15.1 15-0* Operating Data

ALARM 38, Internal faultWhen an internal fault occurs, a code number defined inthe table below is displayed.TroubleshootingCycle powerCheck that the o

Pagina 117 - * Log always

ALARM 50, AMA calibration failedContact your Danfoss supplier or Danfoss ServiceDepartment.ALARM 51, AMA check Unom and InomThe settings for motor vol

Pagina 118 - * [ 0 - 0 ]

ALARM 80, Drive initialised to default valueParameter settings are initialised to default settings after amanual reset. Reset the unit to clear the al

Pagina 119 - 3.15.4 15-3* Alarm Log

5 Parameter Lists5.1 Parameter Options5.1.1 Default settings Changes during operation:”TRUE” means that the parameter can be changed while the freque

Pagina 120 - 3.15.6 15-6* Option Ident

5.1.2 0-** Operation and DisplayPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType0-0* Basic Settings0-0

Pagina 121 - 3.16.1 16-1* Motor Status

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType0-81 Working Days ExpressionLimit 1 set-up TRUE - Uint

Pagina 122 - 3.16.2 16-3* Drive Status

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType1-66 Min. Current at Low Speed ExpressionLimit All set

Pagina 123 - 16-5* Ref. & Feedb

5.1.5 3-** Reference / RampsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType3-0* Reference Limits3-02

Pagina 124

Group no. Parameter group:0 Operation/Display1 Load/Motor2 Brakes3 References/Ramps4 Limits/Warnings5 Digital In/Out6 Analog In/Out8 Comm. and Options

Pagina 125

5.1.6 4-** Limits / WarningsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType4-1* Motor Limits4-10 Moto

Pagina 126

5.1.7 5-** Digital In / OutPar.No. #Parameter description Default value 4-set-up Change duringoperationConver-sion indexType5-0* Digital I/O mode5-00

Pagina 127 - HVAC Drive Programming Guide

5.1.8 6-** Analog In / OutPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType6-0* Analog I/O Mode6-00 Liv

Pagina 128 - 3.17.2 18-1* Fire Mode Log

5.1.9 8-** Communication and OptionsPar. No.#Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType8-0* General Setti

Pagina 129 - 3.17.3 18-3* Analog I/O

Par. No.#Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType8-95 Bus Feedback 2 0 N/A 1 set-up TRUE 0 N28-96 Bus F

Pagina 130 - * Analog input 54

5.1.10 9-** ProfibusPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType9-00 Setpoint 0 N/A All set-ups TR

Pagina 131

5.1.11 10-** CAN FieldbusPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType10-0* Common Settings10-00 CA

Pagina 132 - * Linear

5.1.13 13-** Smart Logic ControllerPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType13-0* SLC Settings1

Pagina 133

5.1.14 14-** Special FunctionsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType14-0* Inverter Switching

Pagina 134

5.1.15 15-** Drive InformationPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType15-0* Operating Data15-0

Pagina 135 - 130BA353.10

Use 3-10 Preset Reference as another example:Choose the parameter, press [OK], and use the up/downnavigation keys keys to scroll through the indexed v

Pagina 136

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType15-72 Option in Slot B 0 N/A All set-ups FALSE 0 VisSt

Pagina 137 - * [50 - 150

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType16-50 External Reference 0.0 N/A All set-ups FALSE -1

Pagina 138

5.1.17 18-** Info & ReadoutsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType18-0* Maintenance Log1

Pagina 139 - 3.18.7 20-9* PID Controller

5.1.18 20-** FC Closed LoopPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType20-0* Feedback20-00 Feedbac

Pagina 140 - * [1.0

5.1.19 21-** Ext. Closed LoopPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType21-0* Ext. CL Autotuning2

Pagina 141 - 21-0* Extended CL autotuning

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType21-6* Ext. CL 3 PID21-60 Ext. 3 Normal/Inverse Control

Pagina 142 - * [ par. 21-03

5.1.20 22-** Application FunctionsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType22-0* Miscellaneous2

Pagina 143

Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType22-85 Speed at Design Point [RPM] ExpressionLimit All

Pagina 144 - Reference

5.1.21 23-** Time Based FuntionsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType23-0* Timed Actions23-

Pagina 145 - * [ -999999.999 - par

5.1.22 24-** Application Functions 2Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType24-0* Fire Mode24-

Pagina 146

3 Parameter Description3.1 Parameter Selection3.1.1 Main Menu StructureParameters for the frequency converter are grouped intovarious parameter group

Pagina 147

5.1.23 25-** Cascade Pack ControllerPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType25-0* System Setti

Pagina 148 - * [0.02 - 10.00

5.1.24 26-** Analog I / O Option MCB 109Par.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType26-0* Analog I

Pagina 149 - 148 MG11CD02 - VLT

IndexAAbbreviations... 4Acceleration Time...

Pagina 150

LLanguagePackage 1... 23Package 2...

Pagina 151 - * [1 - 400

WWarning Words... 196IndexVLT® HVAC Drive Programming GuideMG11CD02 -

Pagina 152 - 3.20.3 22-4* Sleep Mode

www.danfoss.com/drives *MG11CD02*130R0318 MG11CD02 Rev. 2011-08-16

Pagina 153 - 152 MG11CD02 - VLT

3.2 Main Menu - Operation and Display - Group 0Parameters related to the fundamental functions of thefrequency converter, function of the LCP buttons

Pagina 154 - * [0 - 100

0-04 Operating State at Power-upOption: Function:Select the operating mode upon reconnectionof the frequency converter to mains voltageafter power do

Pagina 155

0-11 Programming Set-upOption: Function:Select the set-up to be edited (i.e.programmed) during operation; either theactive set-up or one of the inact

Pagina 156 - * [ 0 - par

0-13 Readout: Linked Set-upsArray [5]Range: Function:0 * [0 - 255 ]View a list of all the set-ups linked by means of 0-12 This Set-up Linked to. Th

Pagina 157 - * [0 - 100 %] Example 1:

0-20 Display Line 1.1 SmallOption: Function:[1605] Main Actual Value[%]View the two-byte word sent withthe Status word to the bus Masterreporting the

Pagina 158 - P22-81 0%

0-20 Display Line 1.1 SmallOption: Function:[1666] Digital Output[bin]Binary value of all digital outputs.[1667] Pulse Input #29[Hz]Actual value of t

Pagina 159

3.22 Main Menu - Application Functions 2 - Group 241693.23 Main Menu - Cascade Controller - Group 251753.24 Main Menu - Analog I/O Option MCB 109 - Gr

Pagina 160

0-20 Display Line 1.1 SmallOption: Function:[2138] Ext. 2 Feedback[Unit]The value of the feedback signal forextended Closed Loop Controller 2[2139] E

Pagina 161 - * All days

130BT105.110Custom Readout (Value)P 16-09Custom ReadoutUnit P 0-30Max valueP 0-32Min valueP 0-31Motor SpeedMotor SpeedHigh limitP 4-13 (RPM)P 4-14 (Hz

Pagina 162 - 23-1* Maintenance

0-32 Custom Readout Max ValueRange: Function:100.00 Custom-ReadoutUnit* [ par. 0-31 -999999.99CustomRea-doutUnit]This parameter sets the maxvalue to

Pagina 163 - * Motor bearings

0-42 [Auto on] Key on LCPOption: Function:[0] Disabled No function[1] * Enabled [Auto on] Key is enabled[2] Password Avoid unauthorized start in Auto

Pagina 164 - * Do not

0-65 Personal Menu PasswordRange: Function:200 * [0 - 999 ] Define the password for access to the MyPersonal Menu via the [Quick Menu] key. If 0-66

Pagina 165 - 3.21.3 23-5* Energy Log

0-81 Working DaysArray with 7 elements [0] - [6] displayed below parameternumber in display. Press OK and step between elements bymeans of ▲ and ▼ bu

Pagina 166 - 3.21.4 23-6* Trending

3.3 Main Menu - Load and Motor - Group 13.3.1 1-0* General SettingsDefine whether the frequency converter operates in openloop or closed loop.1-00 C

Pagina 167

1-06 Clockwise DirectionThis parameter defines the term “Clockwise” corresponding tothe LCP direction arrow. Used for easy change of direction ofshaf

Pagina 168 - 3.21.5 23-8* Payback Counter

1-10 Motor construction[0]Asynchron[1] PM Motornon salient4-13 Motor speed high limit [rpm]x x4-14 Motor speed high limit [Hz]x x4-16 Torque limit mot

Pagina 169 - * [0 - 0

3.3.4 1-2* Motor DataParameter group 1-2* comprises input data from thenameplate on the connected motor.NOTEChanging the value of these parameters aff

Pagina 170 - 3.22.1 24-0* Fire Mode

1 IntroductionVLT® HVAC DriveFC 100 SeriesThis guide can be used with allVLT® HVAC Drive frequencyconverters with software version3.7x.The actual soft

Pagina 171

1-28 Motor Rotation CheckOption: Function:Following installation and connection of themotor, this function allows the correct motorrotation direction

Pagina 172 - * [-100.00

IdRsPar. 1-30LdPar. 1-37ωsLqIq-+UdIdRsPar. 1-30Lq=LdPar. 1-37ωsLdId-++-Par. 1-40ωsλPMUqd-axis equivalent circuitq-axis equivalent circuit130BC056.10Il

Pagina 173 - * Trip, Critical

NOTEThis parameter is only active when 1-10 Motor Constructionhas the value PM, non-salient SPM [1] (Permanent MagnetMotor).Stator resistance and d-ax

Pagina 174

3.3.6 1-5* Load Indep. Setting1-50 Motor Magnetisation at Zero SpeedRange: Function:100%* [0 -300%]Use this parameter along with 1-51 Min SpeedNorma

Pagina 175 - * [-100.0000

3.3.7 1-6* Load Depend. Setting1-60 Low Speed Load CompensationRange: Function:100 %* [0 - 300%]Enter the % value to compensate voltage inrelation

Pagina 176

1-66 Min. Current at Low SpeedRange: Function:Size related* [ 1. - 200.%]Enter the minimum motor current atlow speed.Increasing this current improv

Pagina 177 - * [ 2

motor at that speed and resume normal operation. Pleaserefer to description of 1-70 PM Start Mode forrecommended settings.Current limitations of the F

Pagina 178

1-79 Compressor Start Max Time to TripRange: Function:5.0 s* [0.0 -10.0 s]The time, from the start signal is given untilthe speed exceeds the speed

Pagina 179

NOTEThis parameter is only available if 0-02 Motor Speed Unit isset to [Hz].3.3.11 1-9* Motor Temperature1-90 Motor Thermal ProtectionOption: Functio

Pagina 180 - 25-4* Staging Settings

1-93 Thermistor SourceOption: Function:Select the input to which the thermistor(PTC sensor) should be connected. Ananalog input option [1] or [2] can

Pagina 181

1.1.4 Abbreviations Alternating current ACAmerican wire gauge AWGAmpere/AMP AAutomatic Motor Adaptation AMACurrent limit ILIMDegrees Celsius°CDirect c

Pagina 182 - 25-5* Alternation Settings

3.4 Main Menu - Brakes - Group 23.4.1 2-0* DC-BrakesParameter group for configuring the DC brake and DChold functions.2-00 DC Hold/Preheat CurrentRa

Pagina 183 - * [ par

3.4.2 2-1* Brake Energy Funct.Parameter group for selecting dynamic braking parameters.Only valid for frequency converters with brake chopper.2-10 Br

Pagina 184 - 3.23.6 25-9* Service

2-15 Brake CheckOption: Function:Select type of test and monitoring function tocheck the connection to the brake resistor, orwhether a brake resistor

Pagina 185 - 184 MG11CD02 - VLT

3.5 Main Menu - Reference/Ramps - Group 33.5.1 3-0* Reference LimitsParameters for setting the reference unit, limits and ranges.Please see also para

Pagina 186

3-13 Reference SiteOption: Function:Select which reference site to activate.[0] * Linked toHand / AutoUse local reference when in Hand mode; orremote

Pagina 187 - 3.24.1 26-0* Analog I/O Mode

3-17 Reference 3 SourceOption: Function:Select the reference input to be usedfor the third reference signal. 3-15 Reference 1 Source, 3-16 Reference2

Pagina 188

3-42 Ramp 1 Ramp Down TimeRange: Function:Sizerelated* [ 1.00 -3600.00 s]Enter the ramp-down time, i.e. thedeceleration time from 1-25 MotorNominal

Pagina 189 - 3.24.5 26-4* Analog Out X42/7

3-57 Ramp 2 S-ramp Ratio at Decel. StartRange: Function:50 %* [Applicationdependant]Enter the proportion of the totalramp-down time (3-52 Ramp 2 Ra

Pagina 190 - 3.24.6 26-5* Analog Out X42/9

3.5.6 3-9* Digital Pot.MeterThe digital potentiometer function allows the user toincrease or decrease the actual reference by adjusting theset-up of t

Pagina 191 - * [0.00 - 100.00

3.6 Main Menu - Limits/Warnings - Group 43.6.1 4-1* Motor LimitsDefine torque, current and speed limits for the motor, andthe reaction of the frequen

Pagina 192 - 4 Troubleshooting

fMMotor frequency.fMAXMaximum motor frequency.fMINMinimum motor frequency.fM,NRated motor frequency (nameplate data).IMMotor current (actual).IM,NRate

Pagina 193

4-17 Torque Limit Generator ModeRange: Function:100.0%* [ 0.0 -1000.0 %]Enter the maximum torque limit forgenerator mode operation. The torquelimit

Pagina 194

NOTEAny changes in 4-13 Motor Speed High Limit [RPM] will resetthe value in 4-53 Warning Speed High to the same value asset in 4-13 Motor Speed High L

Pagina 195 - Troubleshooting

3.6.4 Semi-Automatic Bypass Speed Set-upThe Semi-Automatic Bypass Speed Setup can be used tofacilitate the programming of the frequencies to beskipped

Pagina 196 - 4.1.1 Alarm Words

3.7 Main Menu - Digital In/Out - Group 53.7.1 5-0* Digital I/O ModeParameters for configuring the input and output usingNPN and PNP.5-00 Digital I/O

Pagina 197 - 4.1.2 Warning Words

[0] No operation No reaction to signals transmitted toterminal.[1] Reset Resets frequency converter after a TRIP/ALARM. Not all alarms can be reset.[2

Pagina 198 - 4.1.3 Extended Status Words

down to be used. If Speed up/down isused, the speed change always followsramp 2 (3-51 Ramp 2 Ramp Up Time and 3-52 Ramp 2 Ramp Down Time) in the range

Pagina 199 - 4.1.4 Fault Messages

[66] Sleep Mode Forces frequency converter into Sleep Mode(see parameter group 22-4*). Reacts on therising edge of signal applied![68] Timed ActionsDi

Pagina 200

5-19 Terminal 37 Safe StopOption: Function:off). When safe stop circuit is reestablished,the frequency converter will continue withoutmanual reset, u

Pagina 201 - 200 MG11CD02 - VLT

[19] Belowfeedback lowThe feedback is below the limit set in 4-56 Warning Feedback Low.[20] Abovefeedback highThe feedback is above the limit set in 4

Pagina 202

Action [43] Set dig. out. F high is executed.The input will go low whenever the SmartLogic Action [37] Set dig. out. F low isexecuted.[160] No alarm T

Pagina 203 - 202 MG11CD02 - VLT

Digital InputsThe digital inputs can be used for controlling variousfunctions of the frequency converter.Digital OutputsThe frequency converter featur

Pagina 204

[200] FullCapacityAll pumps running and at full speed[201] Pump1RunningOne or more of the pumps controlled by theCascade Controller are running. The f

Pagina 205 - 5 Parameter Lists

5-40 Function RelayArray [8](Relay 1 [0], Relay 2 [1]Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).Select options to define the function

Pagina 206

130BA076.10(RPM)Ref.Low freq.P 5-50/P 5-55Input(Hz)Highref.valueP 5-53/p 5-58High freq.P 5-51/P 5-56Lowref.valueP 5-52/p 5-575-50 Term. 29 Low Freque

Pagina 207 - 5.1.3 1-** Load / Motor

3.7.8 5-6* Pulse OutputsParameters for configuring the scaling and outputfunctions of pulse outputs. The pulse outputs aredesignated to terminals 27 o

Pagina 208 - 5.1.4 2-** Brakes

5-66 Terminal X30/6 Pulse Output VariableSelect the variable for read-out on terminal X30/6.This parameter is active when option module MCB 101 isins

Pagina 209 - 5.1.5 3-** Reference / Ramps

5-97 Pulse Out #X30/6 Bus ControlRange: Function:0.00 %* [0.00 - 100.00 %] Contains the frequency to apply tothe digital output terminal 27, whenit

Pagina 210 - 5.1.6 4-** Limits / Warnings

3.8 Main Menu - Analog In/Out - Group 63.8.1 6-0* Analog I/O ModeParameter group for setting up the analog I/O configu-ration.The frequency converter

Pagina 211 - 5.1.7 5-** Digital In / Out

3.8.2 6-1* Analog Input 1Parameters for configuring the scaling and limits foranalog input 1 (terminal 53).6-10 Terminal 53 Low VoltageRange: Functio

Pagina 212 - 5.1.8 6-** Analog In / Out

6-22 Terminal 54 Low CurrentRange: Function:4.00mA* [ 0.00 -par. 6-23mA]Enter the low current value. This referencesignal should correspond to the l

Pagina 213

6-37 Term. X30/11 Live ZeroOption: Function:This parameter makes it possible to disable theLive Zero monitoring. E.g. to be used if theanalog outputs

Pagina 214

VVCplusIf compared with standard voltage/frequency ratio control,Voltage Vector Control (VVCplus ) improves the dynamicsand the stability, both when t

Pagina 215 - 5.1.10 9-** Profibus

6-50 Terminal 42 OutputOption: Function:[131] Reference 4-20mA Minimum Reference - MaximumReference[132] Feedback 4-20mA-200% to +200% of 20-14 Maxim

Pagina 216 - 5.1.12 11-** LonWorks

EXAMPLE 2:Variable= FEEDBACK, range= -200% to +200%Range needed for output= 0-100%Output signal 0 or 4mA is needed at 0% (50% of range) -set 6-51 Term

Pagina 217

6-63 Terminal X30/8 Output Bus ControlRange: Function:0.00 %* [0.00 - 100.00 %] Contains the value to apply to theoutput terminal, when it isconfig

Pagina 218

3.9 Main Menu - Communications and Options - Group 83.9.1 8-0* General Settings8-01 Control SiteOption: Function:The setting in this parameter overr

Pagina 219

8-05 End-of-Timeout FunctionOption: Function:until 8-06 Reset Control Timeout toggles. Thenthe frequency converter resumes its originalset-up.[1] * R

Pagina 220 - 5.1.16 16-** Data Readouts

8-13 Configurable Status Word STWOption: Function:[72] Logic Rule 2 See parameter group 13-4*. If Logic Rule2 is evaluated as TRUE, the output will g

Pagina 221

8-31 AddressRange: Function:Size related* [ 1. - 255. ] Enter the address for the FC(standard) port.Valid range: 1 - 126.8-32 Baud RateOption: Fun

Pagina 222

3.9.5 8-5* Digital/BusParameters for configuring the control word Digital/Busmerging.NOTEThese parameters are active only when 8-01 Control Site isset

Pagina 223 - 5.1.18 20-** FC Closed Loop

8-56 Preset Reference SelectOption: Function:[0] DigitalinputActivates Preset Reference selection via adigital input.[1] Bus Activates Preset Referen

Pagina 224 - 5.1.19 21-** Ext. Closed Loop

8-91 Bus Jog 2 SpeedRange: Function:200 RPM* [ 0 - par. 4-13RPM]Enter the jog speed. This is a fixedjog speed activated via the serialport or field

Pagina 225

activated in error, be delayed or fail to occurentirely. When used in situations where safety iscritical, e.g. when controlling the electromagneticbra

Pagina 226

3.10 Main Menu - Profibus - Group 99-15 PCD Write ConfigurationArray [10]Option: Function:Select the parametersto be assigned to PCD3 to 10 of thete

Pagina 227

PB-16 PCD Read ConfigurationArray [10]Option: Function:[1656] Feedback 3 [Unit][1660] Digital Input[1661] Terminal 53 Switch Setting[1662] Analog Inp

Pagina 228

9-23 Parameters for SignalsArray [1000]Option: Function:[1601] Reference [Unit][1602] Reference [%][1603] Status Word[1605] Main Actual Value [%][160

Pagina 229

9-53 Profibus Warning WordRange: Function:0 * [0 - 65535 ] This parameter displays Profibus communi-cation warnings. Please refer to the ProfibusOp

Pagina 230

9-80 Defined Parameters (1)Array [116]No LCP accessRead onlyRange: Function:0 * [0 - 9999 ] This parameter displays a list of all the definedfreque

Pagina 231

3.11 Main Menu - CAN Fieldbus - Group 103.11.1 10-** DeviceNet and CAN Fieldbus3.11.2 10-0* Common Settings10-00 CAN ProtocolOption: Function:[1] *

Pagina 232

10-11 Process Data Config WriteOption: Function:[417] Torque Limit Generator Mode[590] Digital & Relay Bus Control[593] Pulse Out #27 Bus Control

Pagina 233 - 232 MG11CD02 - VLT

10-13 Warning ParameterRange: Function:0 * [0 - 65535 ] View a DeviceNet-specific Warning word. Onebit is assigned to every warning. Please referto

Pagina 234

3.12 Main Menu - LonWorks - Group 11Parameter group for all LonWorks specific parameters.Parameters related to LonWorks ID.11-00 Neuron IDRange: Fun

Pagina 235 - *MG11CD02*

3.13 Main Menu - Smart Logic - Group 133.13.1 13-** Prog. Features Prog. FeaturesSmart Logic Control (SLC) is essentially a sequence of userdefined a